DESIGN CONCEPT
The Rain
Screen principle is a superior method for wall construction, to prevent
water leakage, and provide a weather resistant exterior design.
The exterior wall panel is still intended to deflect most of the
water that contacts the wall. However,
a one inch cavity is provided behind the wall panels.
If water does penetrate the facade, it reaches the cavity and
cannot move further into the wall assembly.
Instead, water in the cavity will drain down the inside face of
the wall panel or on the waterproof wall membrane at the other side of
the cavity, and it will be deflected and drained out of the wall
assembly. In practice the
cavity acts as a capillary break to remove the capability of water to
stagnate inside the walls. Therefore,
this eliminates the need to caulk the panel joints, as the outer wall
panels are not completely sealed.
Combining
the beauty of Petrarch panels with the forward thinking of Rain Screen
technology, allows the architect to design without the need for exterior
caulking. Utilizing Rain
Screen technology, Petrarch architectural panels are attached to an
aluminum frame system over the watertight wrapping of the building.
This creates a back-ventilated, pressure equalized system that of
itself aids in moving moisture away from the building.
With the weather barrier behind the system away from the damaging
effects of weather, your project will be watertight year after year
without the risk of a caulk joint failure.
In general, only minor modifications to conventional studwall
construction are required. Care
should be given in the selection of materials to contribute to a flat,
aesthetically pleasing finished installation.
Exterior sheathing, protected by the weather barrier, provides a
leveling plane for the panel assembly and functions as a secondary
barrier to air and water infiltration.
Extruded Aluminum Hat Channels are positioned continuously at
each panel perimeter and to intermediate Extruded Aluminum J-Channels,
not more than 24” O.C. These
extrusions have a 1/8” wall thickness.
The Extruded Aluminum Hat and J-Channels are firmly fastened
through the weather barrier
and sheathing into the horizontal steel
backing plate (18 gauge min.)*, using Stainless Steel fasteners.
For convenience, slots are provided in the extrusions approx.
every 24 inches for attaching to the building.
*For installations with outboard insulation with continuous Z-channels,
the steel backing plate is not necessary.
SYSTEM LIMITATIONS
This system
is applicable to 5/16” Petrarch panels, maximum size 47 3/4” x 119
3/4”, used on buildings designed for maximum wind loads of 40 pounds
per square foot. (For wind
loads over 40 pounds, contact CEP Panels Technical Department.)
The system is stick built, field assembled, and set from exterior
staging.
Success in setting Petrarch panels in a Rain
Screen system is dependent upon care in the selection of materials for
both performance and compatibility, a thoroughly planned installation
procedure, plus, of course, careful workmanship and quality control.
CEP’s technical staff should be consulted in early design or
construction stages to review all construction applications.
DESIGN
NOTES
1. Subwall
Construction
Given design
loading conditions, deflection of the wood or light-gauge steel studwall
must be limited to L/240. Control
and relief joints, as applicable to the structure, must be incorporated
to prevent transfer of undue stresses (caused by structural movement,
deflection, and hygrometric and thermal expansion and contraction) to
the exterior wall panels. The
wall must be laid out with a horizontal steel backing plate (18 gauge
min.)* to accommodate structural fasteners for each Extruded Aluminum
Hat or J-Channel, in addition to attachment of exterior sheathing and
any required interior-wall surfaces.
*For installations with outboard insulation with continuous Z-channels,
the steel backing plate is not necessary.
The sub wall construction should be erected plumb and true with
the maximum variation from the true plane not to exceed 1/8” in 10’.
As a barrier to air and water infiltration into the finished wall
assembly, the sheathing should be protected by a layer of watertight
weather barrier.
2. Panel
Layout
Cut-to-size
panels are taken from standard stock sheets so the net installed cost is
directly affected by the gross square footage of stock sheets required
for the project. To minimize
waste, it is important to plan finished modules which take full
advantage of the available standard sizes, 47 3/4” x 95 3/4” or 119
3/4”.
A more
complete description on size and color can be found in the current CEP
Panels, Inc. brochure, and the general white paper with typical product
performance and test data.
3. Aluminum
Extruded Channels & Vent Screen
Clean, crisp
joinery maintains an architectural integrity unmatched by other systems.
Aluminum Hat Channels and J-Channel extrusions (as appropriate
for each joinery condition on the project) are made of mill finish
aluminum, having a 1/8” wall thickness.
The extrusions can have an anodized finish or be Kynar painted.
Bearing surfaces are dimensioned to allow generous clearances, including
cutting and erection tolerances, plus provide proper contact area.
The Vent
Screen is made of Aluminum, and has generous slots for air flow and
water drainage. (See
Base drawing #7 for installation details).
The Vent Screen can also be used over windows or doors. (See
drawing #12 for installation details).
The drawings on Pages 4, show details of the Extruded Aluminum Hat
Channel and Extruded Aluminum J-Channel.
Available in 10’ lengths. The
Hat Channel is used for the Vertical Joint between two adjoining
Petrarch architectural panels. The
J-Channel is used as the center support or vertical Mid-panel. A
clearance of 3/8” min. must be maintained between all vertical and
horizontal wall panel placement.

Extruded
channels are required continuously at each panel perimeter and to
intermediate mid-panel vertical joint not more than 24” O.C.
In this system, the main
vertical joint and vertical mid-panel joint run continuously. Allow
a min. of 1/4" clearance for coping, and a min. of 3/8” clearance
from the base sill. The
erection sequence begins with placement of the Vent Screen, the Vertical
Hat and J-Channel extruded parts; followed by installation of the
Petrarch architectural wall panels.
Extruded channels are fastened with Stainless Steel screws,
through the sheathing into the metal studs or other solid framing
members. (Subject to
approval by Project Engineer.) Petrarch
architectural panels are secured to the framing with Stainless
Steel screws in a variety of methods, either exposed or hidden.
Wall panel fasteners are located within 1” of both ends of each
length and no more than 24” O.C. in between.
Actual spacing depends on design loads, panel size and shape, and
stud type or gauge.
Typically, thermal expansion and contraction can be anticipated to
be equal at both ends of a length of extruded channel.
The extrusions are attached through generously slotted holes.
Channel lengths must be dimensioned, cut, and erected to allow
free-floating thermal movement over the temperature gradient to which
the installation will be exposed. The
aluminum extrusions have a similar thermal coefficient of expansion to
that of the Petrarch wall panels. However,
in planning, extrusion lengths should be dimensioned as if they were
independent and unrestrained, using aluminum’s 13.0 X 10-6 in/in
ºF coefficient of expansion. A
3/8” gap should be allowed between abutting parts both vertical and
horizontal. The Aluminum
Extrusions for framing are supplied by CEP Panels, Inc. For more
information, contact:
CEP Panels, Incorporated
22 East Chicago Avenue, Suite 210
Naperville
,
Illinois
60540
Tel: (800)
450-6099
Tel: (630) 355-4040
Fax: (630) 355-4995
Email:
info@cep-panels.com
4. Inspection,
Maintenance and Cleaning
A Rain
Screen system should be inspected on a routine basis after installation
to assure that damage, which could affect its structural integrity, has
not occurred. The inspection
program should be in accordance with the responsible structural
engineer’s recommendations. A
minimum schedule would be to inspect twice in the first year and once a
year thereafter, supplemented by inspections which reasonable judgment
would deem prudent following such occurrences as a severe storm,
vandalism, civil disorder, or the like.
Appropriate protective measures and corrective steps should be
promptly implemented anytime structural damage is discovered.
To keep the installation looking clean, the owner should include
panel washing in his annual maintenance schedule, perhaps in conjunction
with window washing. The
actual schedule will vary depending on factors such as the occupation
and use of the building, location relative to atmospheric and
environmental conditions, and the relationship of the wall panels to
surrounding materials. Scrubbing
with a solution of mild detergent or soap and water, followed by a clean
water rinse, using standard commercial cleaning techniques, is all that
is normally required.
INSTALLATION NOTES
1. Panel
Characteristics
All
installation crew members should be familiarized with the
characteristics of Petrarch architectural
panels. To a large degree,
the responsibility for an aesthetically pleasing, trouble-free
installation rests with the installer.
The final product is often judged on the basis of the
installer’s skill and workmanship, and touch up.
For instruction on receiving, storage, material handling, and
field fabrication, refer to the general CEP product white paper.
2. Subwall
Inspection
Prior to the
installation of the panels, the subwall must be inspected to assure that
it is in good condition. The
subwall must be plumb and true, with maximum variation from true plane
no more than 1/8” in 10’. Defects must be corrected before
proceeding to achieve a flat solid installation.
3. Panel
Lay Out
Measure the
wall to determine exact panel locations and mark the positions of all
Vertical Hat and J-Channel Extrusions according to the shop drawings.
Vertical channels run continuously and must be solidly attached
over the watertight weather barrier to the sheathing and Horizontal
Steel Backing Plate. Vertical
channels must be positioned exactly because they directly influence the
final locations of the panels on the wall.
Erection tolerances for other parts can be +/- 1/8”.
If
intermediate stiffeners are included in the design, install stiffener
plates. These may be located
with more generous tolerances.
In all
cases, allow for loose abutment and planned-for expansion clearances.
Use one screw in each length as a stake and set all other
fasteners through generously oversized or slotted holes.
Fasten at each end leaving no more than 16” O.C. in between.
4.
Panel Preparation
Confirm that
the panel is in good condition and cut to the proper size.
Secure wall panels in place using appropriate fasteners as noted
earlier.
5. Quality
Control
Finally, it
is strongly recommended that the project specifications call for a job
site meeting of representatives of CEP, the architect, general
contractor and the installing sub-contractor prior to the start of panel
installation.
NOTE:
The
installation of Petrarch panels using the Rain Screen system must
conform to this design and installation data paper, dated June, 2007, or
all warranties are void.
This CEP design and installation data paper
supersedes all installation instructions.
Check for later additions.
ILLUSTRATIONS
CEP Panels is pleased to provide detailed illustrations for Rain
Screen Installation.
You'll find drawings for the following configurations:
- Vertical
- Vertical Mid-point
- Horizontal
- Horizontal Mid-point
- Coping
- Base
- Inside Corner
- Outside Corner
- Window/Door Head
- Window/Door Jam
- Window/Door Sill
Rain Screen Drawings
While all the Rain Screen drawings are below for quick viewing,
a Portable Document File is available for printing. Click on
the image at top right. |